Yaskawa F7 to L1000A User Manual
Page 44

(Header Title) Application Note
Doc#: PL.L1000A.01 Copyright Yaskawa Electric America, Inc.
©2010 www.yaskawa.com September 9, 2010 44 of 57
Subject: Transition Guide
Product: L1000A
Document: PL.L1000A.01
Title: Product Transition Guide – F7 to L1000A
Product Transition Guide – F7 to L1000A
F7
L1000A
Parameter Name
Parameter
Default
Setting
Record
Parameter
Default
Comments:
Gray shading indicates default setting.
Digi
tal Outp
ut
s
Terminal P2 Function
Selection
─
─
H2-05 F
Terminal A1 Signal Level
Selection
H3-01 0 H3-01 0
Terminal A1 in L1000A is multi-functional.
F7 L1000A
H3-01 H3-01
0: 0 to +10 V
0: 0 to +10 V (uses lower limit)
1: -10 to 10 V
1: 0 to ±10 V (no lower limit)
Terminal A1 Function
Selection
─
─
H3-02 0
─
Terminal A1 Gain Setting
H3-02
100.0%
H3-03
100.0%
F7 L1000A
Setting Range
0.0 % to 1000.0 %
-999.9 % to 999.9%
Analog Inpu
ts
Terminal A1 Bias Setting
H3-03
0.0%
H3-04
0.0%
F7 L1000A
Setting Range
-100.0 % to 100.0 %
-999.9 % to 999.9%
Terminal A3 Signal Level
Selection
H3-04 0 ─
─
No corresponding parameter in L1000A.