Appendix 3- parameter cross reference, Parameter name – Yaskawa GPD506/P5 to P7 User Manual

Page 36

Advertising
background image


Appendix 3- Parameter Cross Reference

Page

36

of 48

GPD506/P5 Parameter

P7 Parameter

Param

No.

Nxxx

Parameter

Name

Description or Selection

Description or Selection

Parameter

Name

Param.

No.

(con’t)

037


Multi-function
contact input 2
(terminal S3)


Set range: 2-28
(It is the same as constant n036)

60: Motor Preheat
Applies current to create heat to avoid
condensation
Closed = Apply amount of current as set in
parameter b2-09
61: Speed Search 1
When closed as a run command is given,
drive does a speed
search starting at maximum frequency (E1-
04).
62: Speed Search 2
When closed as a run command is given,
drive does a speed
search starting at speed command.
64: Speed Search 3
When opened, the Drive performs a
baseblock (motor coasts).
When closed, the Drive performs Speed
Search from set
frequency.
67: Com Test Mode - Used to test RS-
485/422 interface.
68: High Slip Braking - Closed = Drive
stops using High Slip
Braking regardless of run command status.
69: Jog2 - Closed = Drive runs at speed
command entered into
parameter d1-17. Direction determined by
fwd/rev input.
3-wire control Only.
6A: Drive Enable - Closed = Drive will
accept run command.
Open = Drive will not run.
If running, drive will stop per b1-03.
Run Command must be cycled
6B: Com/Inv Sel - Selects source of Speed
Command and
Sequence.
Closed = Serial Communication (R+,R-
,S+,S-), Open = b1-01
& b1-02
6C: Com/Inv Sel 2 - Selects source of
Speed Command and
Sequence.
Closed = b1-01 & b1-02, Open = Serial
Communication
(R+,R-,S+,S-)
6D: Auto Mode Sel - Hand/Auto Selection
- Closed = Auto, Open
= Hand
6E: Hand Mode Sel - Hand/Auto Selection
- Closed = Hand,
Open = Auto
70: Drv Enbl. Same as 6A except a run
command is accepted


Multi-Function Digital Input
Terminal S3 Function
Selection


H1-01

038

Multi-function contact input 3
(terminal S4)

Set range: 2-28
(It is the same as constant n036)

0-70

Same selections as H1-01

Multi-Function Digital Input
Terminal S4 Function
Selection

H1-02

039

Multi-function contact input 4
(terminal S5)

Set range: 2-28
(It is the same as constant n036)

0-70

Same selections as H1-01

Multi-Function Digital Input
Terminal S5 Function
Selection

H1-03

040

Multi-function contact input 5
(terminal S6)

Set range: 2-29

0-70

Same selections as H1-01

Multi-Function Digital Input
Terminal S6 Function
Selection

H1-04