Appendix 3- Parameter Cross Reference
Page
46
of 48
GPD506/P5 Parameter
P7 Parameter
Param
No.
Nxxx
Parameter
Name
Description or Selection
Description or Selection
Parameter
Name
Param.
No.
115
KVA selection
Set unit: 1
Set range: PC5 (0~8, 20~29),
GPD506/P5(9~F, 2A~35)
0 to FF
Sets the kVA of the Drive. Enter the
number based on Drive model number. Use
the last four digits of the model number.
CIMR-P7U
.
This parameter only needs to be set when
installing a new control board. Do not
change for any other reason.
Refer to Table B.1. in the P7 Instruction
Manual
Drive/kVA Selection
o2-04
116
CT/VT selection
0: Constant Torque selection
1: Variable Torque selection
Selects Drive’s rated input and output
current, overload capacity, carrier
frequency, current limit, and maximum
output frequency. See Introduction for
details.
1: Normal Duty 1
2: Normal Duty 2
Reduced Current Rating
Standard Current Rating
C6-01