Appendix 3- Parameter Cross Reference

Page

46

of 48

GPD506/P5 Parameter

P7 Parameter

Param

No.

Nxxx

Parameter

Name

Description or Selection

Description or Selection

Parameter

Name

Param.

No.

115

KVA selection

Set unit: 1
Set range: PC5 (0~8, 20~29),
GPD506/P5(9~F, 2A~35)

0 to FF
Sets the kVA of the Drive. Enter the
number based on Drive model number. Use
the last four digits of the model number.
CIMR-P7U

.

This parameter only needs to be set when
installing a new control board. Do not
change for any other reason.
Refer to Table B.1. in the P7 Instruction
Manual

Drive/kVA Selection

o2-04

116

CT/VT selection

0: Constant Torque selection
1: Variable Torque selection

Selects Drive’s rated input and output
current, overload capacity, carrier
frequency, current limit, and maximum
output frequency. See Introduction for
details.
1: Normal Duty 1
2: Normal Duty 2

Reduced Current Rating
Standard Current Rating

C6-01