Appendix 3- parameter cross reference, Parameter name – Yaskawa GPD506/P5 to P7 User Manual
Page 38

Appendix 3- Parameter Cross Reference
Page
38
of 48
GPD506/P5 Parameter
P7 Parameter
Param
No.
Nxxx
Parameter
Name
Description or Selection
Description or Selection
Parameter
Name
Param.
No.
(con’t)
041
Multi-function
contact output 1
(terminal MA-MB-MC)
1A: Reverse Dir - Closes when the drive is
running in the
reverse direction.
1E: Restart Enabled - Closes when the
drive is performing
an automatic restart.
Automatic restart is configured by
parameter L5-01.
1F: Overload (OL1) - Closes before a
motor overload
occurs. (90% of OL1 time)
20: OH Prealarm - Closes when the Drive’s
heatsink
temperature exceeds the setting
of parameter L8-02.
38: Drive Enable - Closes when the drive
enable input is
active.
39: Waiting to Run - Closes during the time
after a run
command is issued, but the Drive is not
running due to
the time set in parameter b1-10.
3A: OH Freq Reduce
3B: Run Src Com/Opt
H2-01