Appendix 3- Parameter Cross Reference

Page

45

of 48

GPD506/P5 Parameter

P7 Parameter

Param

No.

Nxxx

Parameter

Name

Description or Selection

Description or Selection

Parameter

Name

Param.

No.

100

Time of average
KW

Set unit:1 (1=25ms)
Set range: 1-200 (25ms=5.0sec)

0 to 2000
Used to fine-tune the energy savings
function when in V/F control method.

Power Detection Filter Time

b8-05

101

MEMOBUS timeout
detection

0: Timeout detection disabled.
1: Timeout detection enabled.

Enables or disables the communications
timeout fault (CE).
0: Disabled - A communication loss will
not cause a communication fault.
1: Enabled - If communication is lost for
more than 2 seconds, a CE fault will
occur.

Communication Error
Detection
Selection

H5-05

102

MEMOBUS Stop
method selection at
communication error (CE)

0: Deceleration stop
(Decelerate by deceleration time 1)
1: Coast stop
2: Deceleration stop
(Decelerate by deceleration time 2)
3: Continue operation (alarm display)

Selects the stopping method when a
communication timeout fault (CE) is
detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
4: Run at d1-04

Stopping Method after
Communication Error

H5-04

104

MEMOBUS
Slave address

Set unit:1 Set range:0-31
(There is no MEMOBUS communication at
set point =0)

0 to 20 Hex
Selects Drive station node number
(address) for Modbus terminals R+, R-, S+,
S-. The Drive’s power must be cycled for
the setting to take effect.

Drive Node Address

H5-01

105

MEMOBUS
Baud rate selection

0: 2400bps
1: 4800bps
2: 9600bps

Selects the baud rate for Modbus terminals
R+, R-, S+ and S-. The Drive’s power must
be cycled for the setting to take effect.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps

Communication Speed
Selection

H5-02

106

MEMOBUS
Parity selection

0: Parity none
1: Even parity
2: Odd parity

Selects the communication parity for
Modbus terminals R+, R-, S+ and S-. The
Drive’s power must be cycled for the
setting to take effect.
0: No Parity
1: Even Parity
2: Odd Parity

Communication Parity
Selection

H5-03

108

Motor no-load current

Set unit: 1%
Set range: 0-99%
(100%= rated current of motor)

Set to the magnetizing current of the motor
as a percentage of full load amps (E2-01).
This value is automatically set during
rotational Auto-Tuning.

No-Load Current

E2-03

110

Operator Connection Fault
Detect Select

0: Operator connection fault disabled.
1: Operator connection fault enabled.

Determines if the Drive will stop when the
Digital Operator is removed when in
LOCAL mode or b1-02=0.
0: Disabled - The Drive will not stop when
the Digital Operator is removed.
1: Enabled - The Drive will fault (OPR)
and coast to stop when the operator is
removed.

Operation Selection when
Digital
Operator is Disconnected

o2-06

111

Local/remote Change- over
function Select

0: Cycle External run
1: Accept external run

0: Cycle External RUN - If the run
command is closed when switching from
local mode to remote mode, the Drive
will not run.
1: Accept External RUN - If the run
command is closed when switching
from local mode to remote mode, the
Drive will run.

Local/Remote Run Selection

b1-07

112

Low frequency OL
starting point

Set unit: 0.1Hz
Set range: 0.0-10.0Hz

113

Continuous running
level at 0Hz

Set unit: 1%
Set range: 25-100%

This parameter assists in protecting the
output transistors from overheating when
output current is high and output frequency
is low (6Hz and less).
0: Disabled
1: Enabled (L8-18 is active)





OL2 Characteristic Selection
at
Low Speeds

L8-15