9-28 Examples

MSTR Transaction #5


The Control Block and Data Block registers for the fifth MSTR must be loaded with the following
data before the MSTR block is executed. This MSTR will ACCEPT data into Volatile memory and
allow the drive to run after a parameter change on drive #3.

CONTROL BLOCK

Register

Number

Register

Description

Register

Data

Data

Description

40660

Operation Code

0001h

0001h = Write to Multiple Registers

40661

Network Error Code

0000h

The error code returned by Modbus Plus
communications

40662

Number of Registers

0001h

Write to 1 register

40663

Data Register Code

FFDDh

FFDDh = ACCEPT command

40664

Routing 1

0003h

Modbus Plus node address of the drive = 0003h

40665

Routing 2

0001h

End of routing path = 0001h (Modbus Plus
requirement)

40666

Routing 3

0000h

This routing register is not used, must be set to 0

40667

Routing 4

0000h

This routing register is not used, must be set to 0

40668

Routing 5

0000h

This routing register is not used, must be set to 0


DATA BLOCK

Register

Number

Register

Description

Register

Data

Data

Description

40670

ACCEPT data into
Volatile memory

0000h

To ACCEPT data into Volatile memory, set this
register to ‘0’