Chapter 4 metasys n2 point database – Yaskawa P7 Metasys N2 User Manual

Page 25

Advertising
background image

Cable Loss Behavior 4-1

Chapter 4 Metasys N2 Point

Database

This chapter shows the Metasys N2 point database. This database features 100
logical points: 38 Analog Inputs (AI), 32 Analog Outputs (AO), 19 Binary Inputs
(BI) and 11 Binary Outputs (BO). These points configure, control or monitor the
operation of the drive.

Metasys N2 Analog Input (AI) Summary...........................4 – 3

Metasys N2 Analog Output (AO) Summary ......................4 – 4

Metasys N2 Binary Input (BI) Summary............................4 – 5

Metasys N2 Binary Output (BO) Summary .......................4 – 5