Troubleshooting – A - 8

Wiring And Cabling

The network cable is the correct type

Table A.4 - Metasys N2 Cable Specifications

Specification

Description

Cable Configuration

Twisted Shielded Pair

Gauge

18-20 AWG (Solid or Stranded)

Wire Lay

Minimum 6 twists per foot

Shields

100% foil with drain wire

NEC Type

UL Type CMP

Temperature 60

o

C or higher

Cable Lengths Are Within Specified Limits

Cable lengths cannot exceed 500 feet at 9600 baud.

The Network is Terminated Correctly

A bus terminating resistor of 110Ω is available on each drive terminal board and can be applied to the Metasys N2 communication bus by
setting switch S1-1 to the ON position.

In a multi-node system, only those nodes at the end of a bus segment should have terminating resistors. Before applying a terminating
resistor as described above, care should be taken to understand the physical layout of the network and where other resistors might already
be applied. An overloaded or improperly terminated bus may not function properly.

Figure A.2 – Termination Resistor Setting

Table A.5 - Terminating Resistor Switch Setting

Switch Location

Function

Setting Choices

S1-1

RS-422 and RS-485 Terminating Resistance

OFF: No terminating resistance
ON: Terminating resistance of 110

Shield Is Continuous And Both Ends Of The Shield Are Grounded

As each drive is daisy-chained to the next, twist together the shields of the adjoining cables. Do not connect the shield at each drive.
The continuous shield should then be single-point grounded at the field panel.

Cable Is Routed Correctly

Route the cable away from all power and high frequency lines. Routing within a separate conduit is preferred.