Troubleshooting – A - 7

Speed Command Operation Parameter Is Set Correctly

The speed command operation parameter needs to be set for “Serial Com”.

Table A.2 - Speed Command Operation Parameter

Parameter Number

Setting Choices

Setting Descriptions

0 Operator

1 Terminals

2

Serial Com (Metasys N2)

b1-01

3 Option

PCB

Correct and Unique Network Address

Each device on a Metasys N2 network requires its own unique address. The drive also needs to be programmed to accept the Metasys N2
protocol.

Table A.3 - Serial Communication Device Address Parameter

Parameter Number

Setting Range

Setting Description

H5-01

0 to FFh (0 to 255 dec)x

Serial communication device address

H5-08

0 to 2

1: N2 (Metasys)