3 cable entry, 4 power connection, 1 connected system – Emerson NXL UPS Systems User Manual

Page 14: 2 stand-alone system, 3 attached/detached system, Cable entry, Power connection, Connected system, Stand-alone system, Attached/detached system

Advertising
background image

Battery Installation

10

Figure 8

Stand-alone battery cabinets, no Module Battery Disconnect, detached from UPS

2.3

Cable Entry

Cables may enter the battery cabinet from either the top or the bottom. Cable entry is made possible

by installing conduit to the removable plate fitted at the top or bottom. See 3.0 - Installation Draw-

ings.

2.4

Power Connection

Depending on the site layout, the Battery cabinets can be cabled several ways. See Figures 2

through 8.

2.4.1 Connected System

For cabinets that have been ordered as connected (battery cabinets will bolt to each other), the posi-

tive and negative busbars can be bolted together using the supplied bus bar connector extensions. See

Figure 24

2.4.2 Stand-Alone System

For cabinets that are ordered as stand-alone, customer must supply all the interconnecting cables

and hardware. See Table 15 for current ratings and recommended cable sizes.

2.4.3 Attached/Detached System

For battery cabinets that are connecting to a Liebert NXL UPS, Liebert NXL MBD cabinet or Liebert

NXL Junction cabinet (see Figures 2 through 6), cables will run from the positive and negative bus-

bars of the adjacent battery cabinet to the positive and negative DC connections of UPS, MBD or

Junction cabinet.
For attached systems (the cabinets bolt to each other) the cables can run internal to the cabinets and

will be supplied.
For detached systems (the cabinets do not bolt to each other), the cables must be run outside the cab-

inets. The customer must supply all the interconnecting cables and hardware. See Table 15 for cur-

rent ratings and recommended cable sizes.

Wide

Junction

Cabinet

Maximum of four battery
cabinets.
The junction cabinet
provides sufficient conduit
landing space and is
required for all systems in
this configuration.

Liebert

NXL

Battery

Cabinet

Liebert

NXL
UPS

Additional

Liebert

NXL

Battery

Cabinet

Liebert

NXL

Battery

Cabinet

Liebert

NXL

UPS

Additional

Liebert

NXL

Battery

Cabinet

Wide

Junction

Cabinet

Advertising