Table 12, Table 13, Liebert nxl battery cabinet approximate weights – Emerson NXL UPS Systems User Manual

Page 44: Table 14, Junction cabinets

Advertising
background image

Specifications

40

Table 12

Battery cabinet internal breaker selection based on 5 min EOD, amps

Model

Number

Code

Battery Type

Battery Currents for Various Discharge Times

Required Breaker

Thermal Trip Amps

Discharge

Time (Min)

Watts to Discharge

to 1.60V in 5 min.

Amps @ EOD

PR

UPS12-300MR

5

580

363

400

RR

UPS12-350MR

5

672

420

450

UR

UPS12-400MR

5

770

481

500

WR

UPS12-490MR

5

840

525

600

XR

UPS12-540MR

5

952

595

600

PX

HX300-FR

5

591

369

400

RX

HX330-FR

5

678

424

450

UX

HX400-FR

5

771

482

500

WX

HX500-FR

5

941

588

600

Table 13

Liebert NXL Battery Cabinet approximate weights

Battery

Code

Manufacturer

Battery Model

Total Weight

lb (kg)

PR

C&D

Batteries

UPS12-300MR

3910 (1774)

RR

UPS12-350MR

4265 (1935)

UR

UPS12-400MR

4600 2087)

WR

UPS12-490MR

5545 (2515)

XR

UPS12-540MR

5545 (2515)

PX

Enersys

HX300-FR

3760 (1706)

RX

HX330-FR

4200 (1905)

UX

HX400-FR

4760 (2159)

WX

HX500-FR

5750 (2608)

Table 14

Approximate weights, Liebert NXL Module Battery Disconnect and Liebert NXL
Junction Cabinets

Module Battery

Disconnect Cabinet

Junction Cabinet

Cabinet Size

Weight, lb (kg)

Cabinet Size

Weight, lb (kg)

250-400kVA

544 (247)

Narrow

255 (115)

500-750kVA

544 (247)

Wide

400 (180)