Table 9, Liebert nxl junction cabinet specifications, Table 10 – Emerson NXL UPS Systems User Manual

Page 43: Alber battery monitoring option specifications, Table 11

Advertising
background image

Specifications

39

Table 9

Liebert NXL Junction Cabinet specifications

Battery Specifications

Value

Nominal Battery Bus, VDC

480V

Battery Float Voltage, VDC

540V

Minimum EOD Voltage, VDC

384V (for VRLA / Flooded Lead Acid)

Battery Discharging Max current (EOD), A

Table 11

Physical Parameters and Standards

Narrow Liebert NXL Junction Cabinet, Width,

without side panels

, in (mm)

15.5 (393)

Wide Liebert NXL Junction Cabinet, Width,

without side panels

, in (mm)

30.9 (785)

Depth, in (mm)

33.5 (850)

Height, in (mm)

76.8

(1950)

Weight, lb (kg) approx.

Table 14

Color

Charcoal (ZP-0420)

Degree of Protection for UPS Enclosure

IP 20

Standards and Conformities

UL 1778

CSA 22.2 107.3

FCC Part 15, Class A

ISTA Procedure 1H

WEEE

Minimum clearance, Top

24" (610mm)

Minimum clearance, Back

0"

Minimum clearance, Sides

0"

Location of cable entrance

Top or Bottom

Environmental Parameters

Storage Temperature Range, °F (°C)

-13°F to 158°F (-25°C to 70°C)

Operating Temperature Range, °F (°C)

32°F to 104°F (0 to 40°C)

Relative Humidity

Maximum 95% Non-Condensing

(Operating and Non-Operating)

Maximum Altitude above MSL, ft (m)

4920 (1500) (as per IEC 62040/3) -

1% maximum kW derate / 328ft rise between 4900-9800ft

(100m rise between 1500-3000m)

Table 10

Alber battery monitoring option specifications

Electrical Data

Value

Input Voltage

220-600VAC

Input Current

< 0.5A

Frequency

60Hz

Table 11

Currents for Liebert NXL Module Battery Disconnect Cabinet

UPS Rating

Max Battery Current

at End of Discharge

External Breaker

Trip Amps

kVA

kW

250

225

615

700

300

270

737

800

400

360

981

1000

500

450

1224

1600

625

562.5

1526

1600

750

675

1828

2000