Table 7

Liebert NXL Battery Cabinet specifications

Battery Cabinet Parameters

Values

Battery Type

VRLA (Valve Regulated Lead Acid)

Nominal Battery Bus, VDC

480V

Battery Float Voltage, VDC

540V

Minimum EOD Voltage, VDC

384V (for VRLA / Flooded Lead Acid)

Battery Discharging Max current (EOD), A

See Table 12

Physical Parameters and Standards

Width, in. (mm)

without side panels attached

55.1 (1400)

Depth, in. (mm)

33.5 (850)

Height, in. (mm)

76.8 (1950)

Weight, lb (kg) approx.

Table 13

Color

Charcoal (ZP-0420)

Front Door Opening (for serviceability)

More than 180°

Degree of Protection for UPS Enclosure

IP 20 (with and without front door open)

Standards & Conformities

UL 1778

CSA 22.2 107.3

FCC Part 15, Class A

ISTA Procedure 1H

WEEE

Minimum Clearance, Top

24" (610mm)

Minimum Clearance, Back

0"

Minimum Clearance, Sides

0"

Location of Cable Entrance

Top or Bottom

Environmental

Storage Temperature Range, °F (°C)

-13°F to 158°F (-25°C to 70°C)

74°F to 80°F (23-27°C) for optimal battery life

Operating Temperature Range, °F (°C)

32°F to 104°F (0 to 40°C)

74°F to 80°F (23-27°C) for optimal battery life

Relative Humidity

up to 95% Non-Condensing

(Operating and Non-Operating)

Maximum Altitude Above MSL, ft (m)

4920 (1500) (as per IEC 62040/3) -

1% Maximum kW derate / 100m rise between 1500-3000m