Terminal details, liebert battery cabinet, Figure 14 – Emerson NXL UPS Systems User Manual

Page 21

Advertising
background image

Installation Drawings

17

Figure 14 Terminal details, Liebert Battery Cabinet

Note:
1. All dimensions are in inches (mm)
2.. 24" minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates.
5. Control wiring and power wiring must be run in separate conduit.
6. Aluminum and copper-clad aluminum cables are not recommended.
7. All wiring must be in accordance with national and local electrical codes.

1.75

(45)

.56

(14)

1.75 (45)

1.75 (45)

1.75

(45)

1.75

(45)

.53

(14)

See Bus
Termination Detail

Negative Term. Bus (-)

Positive Term. Bus (+)

Top View

Right Side View

Front View

Ground Bus
(See Detail)

* Doors And Covers Removed for Clarity

Ground Bus Detail

+

-

Bus Termination Detail