Table 2 liebert-supplied interconnect wiring, Table 2, Liebert-supplied interconnect wiring – Emerson NXL UPS Systems User Manual

Page 33

Advertising
background image

Installation Drawings

29

Figure 27 Liebert NXL Module Battery Disconnect interconnect wiring to 250-400kVA UPS

Table 2

Liebert-supplied interconnect wiring

Run

From

To

Conductors

A1

UPS - DC+ Busbar

MBD - DC + Busbar

Positive Power - Right Mount

B1

UPS - DC- Busbar

MBD - DC - Busbar

Negative Power - Right Mount

A2

UPS - DC+ Busbar

MBD - DC + Busbar

Positive Power - Left Mount

B2

UPS - DC- Busbar

MBD - DC - Busbar

Negative Power - Left Mount

C *

UPS - GROUND

MBD - GROUND

Ground

D

UPS - External Interface Board (EIB)

MBD - Battery Interface Board (BIB)

CAN Control Cables

* This is used only for detached cabinets. If the cabinets are attached, use the grounding shown in Figure 25.

UPS

D

A1

B1

C

C

D

A1,2

B1, 2

A2

B2

B1, 2

A1, 2

C

UPS - Rear View
DC Bus Connections

Module Battery Disconnect

Top Feed

Top Feed

Top
Feed

Bottom
Feed

Bottom
Feed

Bottom
Feed