Table 5 liebert-supplied interconnect wiring, Battery cabinet, Table 5 – Emerson NXL UPS Systems User Manual

Page 36: Liebert-supplied interconnect wiring

Advertising
background image

Installation Drawings

32

Figure 30 Liebert NXL UPS to Liebert NXL Module Battery Disconnect to Liebert NXL Battery Cabinet

Table 5

Liebert-supplied interconnect wiring

Run

From

To

Conductors

A1

UPS - DC+ Busbar

MBD - DC+ Busbar

Positive Power - RH Mount/

Stand-Alone

B1

UPS - DC- Busbar

MBD - DC- Busbar

Negative Power - RH Mount/

Stand-Aone

A2

UPS - DC+ Busbar

MBD - DC+ Busbar

Positive Power - Left Mount

B2

UPS - DC- Busbar

MBD - DC- Busbar

Negative Power - Left Mount

C*

UPS - Ground

MBD - Ground

Ground

D

UPS - External Interface

Board (EIB)

MBD - Battery Interface Board (BIB)

CAN Control Cables

E

MBD - DC+ Busbar

Battery Cabinet - DC+ Busbar

Positive Power

F

MBD - DC- Breaker

Battery Cabinet - DC- Busbar

Negative Power

G

MBD - Battery Interface

Board (BIB)

Battery Cabinet - Battery

Interface Board (BIB)

CAN Control Cables

H*

MBD - Ground

Battery Cabinet - Ground

Ground

* For detached units only

Top Feed A1, A2, E

F, B1, B2

C,H

Top
Feed

D,G

G

H

F

E

A1

B1

C

D

UPS - Rear View

DC Bus Connections

F

E

B1,2 Bottom

Feed

F

C,H

Bottom
Feed

Bottom
Feed
A1,2,E

A2

B2

Top
Feed

UPS

Battery Cabinet

Modular Battery Disconnect