Top view with door open right side view front view – Emerson NXL UPS Systems User Manual

Page 22

Advertising
background image

Installation Drawings

18

Figure 15 Outline drawing, 250-400kVA, Liebert Module Battery Disconnect

1. All dimensions are in inches (mm).
2. 24" minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates.
5. Control wiring and power wiring must be run in seperate conduit.
6. Aluminum and copper-clad aluminum cables are not recommended.
7. Widths are without side panels. The width is 32.1" (815mm) with side panels.
8.The depth dimension includes the front door and rear panel.

CG

76.9

(1952)

33.5

(850)

30.9

(785)

37.9

(962)

14.4

(367)

19.0

(483)

62.3

(1583)

CG

4.1

(104)

Top View

With Door Open

Right Side View

Front View

Advertising