6 alber monitoring system—optional, Alber monitoring system—optional, External battery room temperature sensor—optional – Emerson NXL UPS Systems User Manual

Page 18

Advertising
background image

Battery Installation

14

2.6

Alber Monitoring System—Optional

The Liebert matching battery cabinet allows installing an optional Alber battery monitoring system

in the cabinet. The Alber battery monitoring continuously checks all critical battery parameters, such

as cell voltage, overall string voltage, current and temperature. Automatic periodic tests of internal

resistance of each battery will verify the battery’s operating integrity. Additional capabilities include

automatic internal DC resistance tests and trend analysis providing the ability to analyze perfor-

mance and aid in troubleshooting.
The Alber monitoring system is installed inside the battery cabinet (see Figure 33). The monitoring

system requires approximately 0.5A, single-phase power.
This power can come from the output of the UPS the battery cabinet is suppling (see Figure 33).
The Alber monitoring system consists of a Controller Module and Data Collector Module (see

Figure 31). One Controller Module can monitor up to six (6) battery cabinets with a Data Collector

Module installed. The Battery cabinet with the Controller Module (battery cabinet #1) must be install

in the position closest to the UPS.
For details about operating the Alber system, see the Alber Monitoring System manual, available at

the Liebert Web Site,

www.liebert.com

2.7

External Battery Room Temperature Sensor—Optional

For systems that do not use Liebert NXL battery cabinets, but have an MBD connected to a battery

string, an optional temperature sensor can be installed to monitor the ambient room temperature.

This sensor is connected to the BIB in the MBD cabinet (see Figure 11). This sensor will allow the

Liebert NXL UPS to perform temperature compensation charging.

Figure 11 Battery temperature sensor control connection

TB1154

Battery Interface Board

(inside MBD Cabinet)

P1153

Advertising