0 installation drawings, Figure 12 outline drawing, liebert battery cabinet, Nstallation – Emerson NXL UPS Systems User Manual

Page 19: Rawings, Right side view, Bottom view

Advertising
background image

Installation Drawings

15

3.0

I

NSTALLATION

D

RAWINGS

Figure 12 Outline drawing, Liebert Battery Cabinet

NOTE:
1. All dimensions are in in. (mm)
2. 24" minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates.
5. Control wiring and power wiring must be run in seperate conduit.
6. Aluminum and copper-clad aluminum cables are not recommended.
7. Widths are with side panels. The width is 55.1" (1400mm) without side panels.
8.The depth dimension includes the front door and rear panel.

TOP VIEW

(Doors Open)

56.3

(1430)

42.8

(1088)

27.7

(705)

16.6

(422)

CG

CG

64.1

(1629)

76.8

(1950)

33.5

(850)

Right
Side
View

3.7

(95)

3

(76)

11.2

(285)

11.2

(285)

8.8

(223)

6.4

(161)

3.7

(95)

1.6

(40)

Typ

28.7

( 730)

8.3

(210)

Bottom View

Front