0 mechanical installation, 1 introduction, 2 preliminary checks – Emerson NXL UPS Systems User Manual

Page 7: 3 environmental considerations, 1 battery room, 2 storage, Echanical, Nstallation, Introduction, Preliminary checks

Advertising
background image

Mechanical Installation

3

1.0

M

ECHANICAL

I

NSTALLATION

1.1

Introduction

This following section describes the requirements that must be taken into account when planning the

positioning and cabling of the Liebert NXL battery equipment.
This chapter is a guide to general procedures and practices that should be observed by the installing

engineer. The particular conditions of each site will determine the applicability of such procedures.

NOTICE

Do not apply electrical power to the UPS equipment before the arrival of the commissioning

engineer.

1.2

Preliminary Checks

Before installing the battery equipment, please carry out the following preliminary checks:

• Visually examine the equipment for transit damage, both internally and externally. Report any

damage to the shipper immediately.

• Verify that the correct equipment is being installed. The equipment supplied has an identification

tag on the back of the main door.

• Verify that the battery room satisfies the environmental conditions stipulated in the equipment

specification, paying particular attention to the ambient temperature and air exchange system.

1.3

Environmental Considerations

1.3.1 Battery Room

Batteries should be mounted in an environment where the temperature is consistent and even over

the whole battery. Temperature is a major factor in determining the battery life and capacity. Typical

battery manufacturer performance data are quoted for an operating temperature between 20 and

25°C (68 and 77°F). Operating above this range will reduce the battery life while operation below this

range will reduce the battery capacity.
Battery Temperature
In a normal installation, the battery temperature should be kept between 15°C and 25°C

(59 and 77°F).

1.3.2 Storage

Should the equipment not be installed immediately, it must be stored in a room for protection against

excessive humidity and or heat sources (see Table 7).

NOTICE

An unused battery must be recharged periodically as recommended by the battery

manufacturer.

NOTE
Keep batteries away from main heat sources or main air inlets etc.