Diagnostics and Troubleshooting

MVI69E-MBTCP ♦ CompactLogix Platform

User Manual

Modbus TCP/IP Enhanced Communication Module

Page 104 of 150

ProSoft Technology, Inc.

May 20, 2015

6.5

Communication Error Codes

Note: If an error code is reported that is not listed below, check with the documentation of the

Modbus device(s) on the module's application ports. Modbus devices can produce device-specific

error codes.

6.5.1 Standard MODBUS Protocol Exception Code Errors

Code

Description

1

Illegal Function Code

2

Illegal Data Address

3

Illegal Data Value

4

Failure in Associated Device

5

Acknowledge

6

Busy, Rejected Message

6.5.2 Module Communication Error Codes

Code

Description

-1

CTS modem control line not set before transmit

-2

Timeout while transmitting message

-11

Timeout waiting for response after request

253

Incorrect slave address in response

254

Incorrect function code in response

255

Invalid CRC/LRC value in response

6.5.3 Command List Entry Errors

Code

Description

-41

Invalid enable code

-42

Internal address > maximum address

-43

Invalid node address (< 0 or > 255)

-44

Count parameter set to 0

-45

Invalid function code

-46

Invalid swap code

Advertising