Because the server interface device is normally serviced at the end of the
controller's scan, the data reflect the register content at the end of the scan.
Some servers limit the quantity of register content provided each scan; thus for
large register quantities, multiple transmissions are made using register content
from sequential scans.

In the example below, the registers 40108 to 40110 have the decimal contents
555, 0, and 100 respectively.

Node
Address

Function
Code

Byte
Count

High
Data

Low
Data

High
Data

Low
Data

High
Data

Low
Data

Error Check
Field

(2 bytes)

0B

03

06

02

2B

00

00

00

64

CRC

7.2.7 Read Input Registers (Function Code 04)

Query
This function retrieves the contents of the controller's input registers from the
Modbus 3x range. These locations receive their values from devices connected
to the I/O structure and can only be referenced, not altered from within the
controller, The addressing allows retrieving up to 125 registers at each request;
however, the specific server device may have restrictions that lower this
maximum quantity. The registers are numbered for zero (30001 = zero, 30002 =
one, and so on). Broadcast mode is not allowed.

The example below requests the contents of register 30009 in server number 11.

Note: This is the structure of the message being sent out to the Modbus network. The byte values
below are in hexadecimal display.

Node

Address

Function

Code

Data Start

Point High

Data Start

Point Low

Data Number

of Points High

Data Number

of Points Low

Error Check
Field

(2 bytes)

0B

04

00

08

00

01

CRC

Response
The addressed server responds with its address and the function code followed
by the information field. The information field contains 1 byte describing the
quantity of data bytes to be returned. The contents of the registers requested
(DATA) are 2 bytes each, with the binary content right justified within each pair of
characters. The first byte includes the high order bits and the second, the low
order bits.