Module configuration parameters, 2 module configuration parameters 3.2.1 module – ProSoft Technology MVI69E-MBTCP User Manual

Page 47

Advertising
background image

MVI69E-MBTCP ♦ CompactLogix Platform

Configuring the MVI69E-MBTCP Using PCB

Modbus TCP/IP Enhanced Communication Module

User Manual

ProSoft Technology, Inc.

Page 47 of 150

May 20, 2015

3.2

Module Configuration Parameters

3.2.1 Module

This section contains general module configuration parameters. In the ProSoft
Configuration Builder (PCB) tree view, expand the MVI69E-MBTCP icon, then

expand

M

ODULE

, and then double-click the

M

ODULE

icon.

Parameter

Value

Description

Module Name

ASCII
characters
(max. 80)

Assigns a name to the module that can be viewed using the
configuration/debug port. Use this parameter to identify the module
and the configuration file.

Read Register Start

0 to 9999

Specifies the starting address of the module's Read Data area.
Data in this area is transferred from the module to the processor.

Read Register Count

0 to 10,000

Specifies the size of the Read Data area.

Write Register Start

0 to 9999

Specifies the start of the Write Data area in module memory. Data
in this area is transferred in from the processor.

Write Register Count

0 to 10,000

Specifies the size of the Write Data area.

Failure Flag Count

0 to 65535

Specifies the number of consecutive backplane transfer failures
that can occur before Modbus communications are halted.

Error/Status Block Pointer

-1 to 9939

Starting register location in the module’s database for the
error/status table. This data must be placed in the read data range
of module memory. If a value of -1 is entered, the error/status data
is not placed in the database. All other valid values determine the
starting location of the data.

This data area includes the module version information and all
server error/status data. Refer to MBTCP.STATUS.GeneralStatus
(page 88) for more information.

Initialize Input Image

Yes or No

This parameter determines if the input image data and the
module’s Read Register Data values are initialized with Read
Register Data values from the processor. If you set the parameter
to No, the Read Register Data values in the module are set to 0
upon initialization. If you set the parameter to Yes, the data is
initialized with Read Register Data values from the processor.
Using this option requires associated ladder logic to pass the data
from the processor to the module.

Block Transfer Size

60, 120 or 240 Specifies the number of words in each block transferred between

the module and processor.

Slot Number

1 to x

Specifies the slot in the CompactLogix rack for the module.

Important: The sum of the Read Register Count and Write Register Count cannot exceed 10,000
total registers. Furthermore, neither the Read Data nor the Write Data area may extend above

module register 9999. The Read Data and Write Data areas must have separate address ranges in

the module database and must not overlap.

Advertising