In the above example, the client's Modbus command to transmit inside the
Modbus packet is as follows.

Server

Address

Function Code Address in Device Reg Count

DEC

01

3

6100

2

HEX

01

03

17 D4

00 02

In the above example the (Enron/Daniel supporting) server's Modbus command
to transmit inside the Modbus packet is as follows.

Server Address Function Code Byte Count

Data

DEC

01

3

8

32.75 275.69

HEX

01

03

08

00 00 42 03 D8 52 43 89

In the above example the (a NON-Enron/Daniel supporting) server's Modbus
command that is transmitted inside the Modbus packet is as follows.

Server Address Function Code Byte Count

Data

DEC

01

3

4

32.75

HEX

01

03

04

00 00 42 03