Led status indicators – ProSoft Technology MVI69E-MBTCP User Manual

Page 94

Advertising
background image

Diagnostics and Troubleshooting

MVI69E-MBTCP ♦ CompactLogix Platform

User Manual

Modbus TCP/IP Enhanced Communication Module

Page 94 of 150

ProSoft Technology, Inc.

May 20, 2015

6.2

LED Status Indicators

ETH

CFG

BP

OK


The LEDs indicate the module’s operating status.

LED

Color

Indication

ETH

Green

Application is running and Ethernet is ready

Off

Application is not running

CFG

Red

Error in configuration

Green

Configuration is OK

Amber

Configuration state

Off

Application is not running or backplane has failed

BP

Red

Processor is not in RUN mode

Green

(Flashing) BP transfer is operational

Amber

Initialization state

Off

Application is not running

OK

Red

Application is not running

Green

Application is running

During module configuration, the OK LED is red and the BP LED is on. If the BP
ACT and OK LEDs blink at a rate of every one-second, this indicates a serious
problem with the module. Call ProSoft Technology Technical Support to arrange
for repairs.

6.2.1 Clearing a Fault Condition

Typically, if the OK LED on the front of the module remains RED for more than
ten seconds, a hardware problem has been detected in the module or the
program has exited.

To clear the condition, follow these steps:

1 Turn off power to the rack.
2 Remove the card from the rack.
3 Verify that all jumpers are set correctly.
4 If the module requires a Compact Flash card, verify that the card is installed

correctly.

5 Re-insert the card in the rack and turn the power back on.
6 Verify correct configuration data is being transferred to the module from the

CompactLogix controller.

If the module's OK LED does not turn GREEN, verify that the module is inserted
completely into the rack. If this does not cure the problem, contact ProSoft
Technology Technical Support.