MBTCP.CONTROL.EventCommand_PLCData

This array allows the processor to dynamically build Modbus commands with
PLC processor data. This feature is meant for periodic execution such as
resetting the clock and zeroing-out counters.

Tag Name

Range

Description

MBTCP.CONTROL.EventCommand
_PLCData.Trigger

0 or 1

Toggle to send Event Command.
0 = Disable, 1 = Enable

MBTCP.CONTROL.EventCommand
_PLCData.ClientID

0 to 19

Client ID associated with the command to be
executed

MBTCP.CONTROL.EventCommand
_PLCData.ServerIPaddress

xxx.xxx.xx
x.xxx

IP address of target Modbus server

MBTCP.CONTROL.EventCommand
_PLCData.ServicePort

502 or
2000

Service port of target Modbus server

MBTCP.CONTROL.EventCommand
_PLCData.SlaveAddress

1 to 255

Slave address of target Modbus TCP/IP to serial
device, for backwards compatibility

MBTCP.CONTROL.EventCommand
_PLCData.ModbusFunctionCode

1,2,3,4,5,6
,15,16

Specifies the Modbus function to be executed
by the command.

MBTCP.CONTROL.EventCommand
_PLCData.DeviceDBAddress

0 to 9999

Specifies the register or digital point address
offset within the Modbus server device. The
MBTCP client reads or writes from/to this
address within the server.

MBTCP.CONTROL.EventCommand
_PLCData.PointCount

1 to 125
(words)
or
1 to 800
(coils)

Specifies the number of registers or digital
points to be associated with the command.
Modbus Function Codes 5 and 6 ignore this field
as they only apply to a single data point.

MBTCP.CONTROL.EventCommand
_PLCData.Data

Data values associated with the command

MBTCP.CONTROL.EventCommand
_PLCData.ErrorStatus

Command status after execution