Diagnostics and Troubleshooting

MVI69E-MBTCP ♦ CompactLogix Platform

User Manual

Modbus TCP/IP Enhanced Communication Module

Page 98 of 150

ProSoft Technology, Inc.

May 20, 2015

5

The module’s default IP address is usually 192.168.0.250. Choose an unused
IP within your subnet, and then click OK.

Important: The temporary IP address is only valid until the next time the module is initialized. For

information on how to set the module’s permanent IP address, see Ethernet 1 (page 54) .

6 Close the ProSoft Discovery Service window. Enter the temporary IP address

in the Ethernet address field of the Connection Setup dialog box, then click
T

EST

C

ONNECTION

to verify that the module is accessible with the current

settings.

7 If the Test Connection is successful, click C

ONNECT

. The Diagnostics window

is now accessible. See Using the Diagnostics Menu in ProSoft Configuration
Builder (page 98) for more information.

6.4

Using the Diagnostics Menu in ProSoft Configuration Builder

ProSoft Configuration Builder (PCB) provides diagnostic menus for debugging
and troubleshooting.
To connect to the module’s Configuration/Debug Ethernet port
1 In the tree view in ProSoft Configuration Builder (PCB), select the MVI69E-

MBTCP module. For instructions on opening and using a project in PCB,
please refer to the chapter Configuring the MVI69E-MBTCP Using PCB
(page 42).