MVI69E-MBTCP ♦ CompactLogix Platform

Configuring the MVI69E-MBTCP Using PCB

Modbus TCP/IP Enhanced Communication Module

User Manual

ProSoft Technology, Inc.

Page 49 of 150

May 20, 2015

Output Offset

0 to 9998

Specifies the offset address into the internal Modbus database
for network requests for Modbus function 1, 5 or 15
commands. For example, if you set the value to 100, an
address request of 0 corresponds to register 100 in the
database.

Bit Input Offset

0 to 9998

Specifies the offset address into the internal Modbus database
for network requests for Modbus function 2 commands. For
example, if you set the value to 150, an address request of 0
returns the value at register 150 in the database.

Holding Register
Offset

0 to 9998

Specifies the offset address in the internal Modbus database
for network requests for Modbus function 3, 6, or 16
commands. For example, if you enter a value of 50, a request
for address 0 corresponds to the register 50 in the database.

Word Input Offset 0 to 9998

Specifies the offset address into the internal Modbus database
for network requests for Modbus function 4 commands. For
example, if you set the value to 150, an address request of 0
returns the value at register 150 in the database.

Connection
Timeout

0 to 1200

Specifies the server’s timeout period if it is not receiving any
new data in the amount of seconds preset.