MVI46-DFCM ♦ SLC Platform

Installing and Configuring the Module

DF1 Communication Module

Page 24 of 103

ProSoft Technology, Inc.

October 20, 2008

Database in SLC

Database in MVI46-DFCM

File

M0 Offset

File

Register

Content

Description

N10:14

15

N32:18

5018

Stop Bits

This parameter sets the number
of stop bits to be used with each
data value sent. Valid value of 1
or 2.

N10:15

16

N32:19

5019

Minimum
Response
Delay

This parameter sets the number
of milliseconds to wait before a
response message is sent out of
the port. This parameter is
required when interfacing to a
slow responding device. Valid
value in the range of 0 to 65535.

N10:16

17

N32:20

5020

RTS On
Delay

This parameter sets the number
of milliseconds to delay after RTS
is asserted before the data will be
transmitted. Valid value in the
range of 0 to 65535.

N10:17

18

N32:21

5021

RTS Off
Delay

This parameter sets the number
of milliseconds to delay after the
last byte of data is sent before the
RTS modem signal will be set
low. Valid value in the range of 0
to 65535.

N10:18

19

N32:22

5022

Use CTS
Line

This parameter specifies if the
CTS modem control line is to be
used. If the parameter is set to 0,
the CTS line will not be
monitored. If the parameter is set
to 1, the CTS line will be
monitored and must be high
before the module will send data.
Normally, this parameter is
required when half-duplex
modems are used for
communication (2-wire).

N10:19

20

N32:23

5023

ENQ Delay

This parameter specifies the
number of milliseconds to wait
after a DLE-ACK is received from
a slave using half-duplex mode
before the DLE-ENQ request is
made for data. Valid value in the
range of 0 to 65535.

N10:20

21

N32:24

5024

Command
Count

This parameter specifies the
number of commands to be
processed for the port. Valid
value of 0 to 100.

Advertising