Database in SLC
Database in MVI46-DFCM
File
M0 Offset
File
Register
Content
Description
N10:14
15
N32:18
5018
Stop Bits
This parameter sets the number
of stop bits to be used with each
data value sent. Valid value of 1
or 2.
N10:15
16
N32:19
5019
Minimum
Response
Delay
This parameter sets the number
of milliseconds to wait before a
response message is sent out of
the port. This parameter is
required when interfacing to a
slow responding device. Valid
value in the range of 0 to 65535.
N10:16
17
N32:20
5020
RTS On
Delay
This parameter sets the number
of milliseconds to delay after RTS
is asserted before the data will be
transmitted. Valid value in the
range of 0 to 65535.
N10:17
18
N32:21
5021
RTS Off
Delay
This parameter sets the number
of milliseconds to delay after the
last byte of data is sent before the
RTS modem signal will be set
low. Valid value in the range of 0
to 65535.
N10:18
19
N32:22
5022
Use CTS
Line
This parameter specifies if the
CTS modem control line is to be
used. If the parameter is set to 0,
the CTS line will not be
monitored. If the parameter is set
to 1, the CTS line will be
monitored and must be high
before the module will send data.
Normally, this parameter is
required when half-duplex
modems are used for
communication (2-wire).
N10:19
20
N32:23
5023
ENQ Delay
This parameter specifies the
number of milliseconds to wait
after a DLE-ACK is received from
a slave using half-duplex mode
before the DLE-ENQ request is
made for data. Valid value in the
range of 0 to 65535.
N10:20
21
N32:24
5024
Command
Count
This parameter specifies the
number of commands to be
processed for the port. Valid
value of 0 to 100.