ProSoft Technology MVI46-DFCM User Manual

Page 54

Advertising
background image

MVI46-DFCM ♦ SLC Platform

Reference

DF1 Communication Module

Page 54 of 103

ProSoft Technology, Inc.

October 20, 2008

5.1.2 Hardware

Specifications

Specification Description

Backplane Current Load

800 ma @ 5V (from backplane)

Operating Temperature

0 to 60°C (32 to 140°F)

Storage Temperature

-40 to 85°C (-40 to 185°F)

Shock

30g operational, 50g non-operational

Relative Humidity

5% to 95% (non-condensing)

Vibration

5 g from 10150 Hz

Processor

Compatible with Rockwell Automation SLC 5/02 M0/M1
capable processors or newer

LED indicators

Module status, Backplane transfer status, Application status,
Serial activity and error LED status

Debug/Configuration port (CFG)

CFG Port (CFG)

RJ45 (DB-9M with supplied cable)
RS-232 only

Configuration Connector

RJ45 RS-232 Connector (RJ45 to DB-9 cable shipped with
unit)

Application Ports
Application Serial port (PRT1,
PRT2) (Serial Modules)

Two RJ45 RS-232/422/485 Application ports

5.1.3 Functional

Specifications

DF1 ports
ƒ

Full and half duplex modes supported

ƒ

CRC and BCC error checking

ƒ

Full hardware handshaking control

ƒ

User-definable module memory usage, supporting the storage and transfer of

up to 5000 registers to/from the control processor

ƒ

Up to 125 word read and write command lengths supported

ƒ

Floating point data movement supported

DF1 Master Protocol Specifications

The ports on the DF1 module can be individually configured as Master ports.
When configured in master mode, the DFCM module is capable of reading and
writing data to remote DF1 devices, enabling the SLC platform to act as a
SCADA sub-master.
ƒ

Command List: Up to 100 commands per Master port, each fully-configurable

for function, slave address, register to/from addressing and word/byte count

ƒ

Status Data: Error codes available on an individual command basis. In

addition, a slave status list is maintained per active master port

ƒ

Polling of Command List: User-configurable polling of commands, including

disabled, continuous, and on change of data (write only)

Advertising