ProSoft Technology MVI46-DFCM User Manual

Page 83

Advertising
background image

Reference MVI46-DFCM

♦ SLC Platform

DF1 Communication Module

ProSoft Technology, Inc.

Page 83 of 103

October 20, 2008

Function Code #5 - Unprotected Write (Basic Command Set)

Column

Parameter

Description

Parameter

1

Enable/Type Word

0=Disabled, 1=Continuous and 2=Conditional.

2

Virtual Database Address

This parameter defines the database address of the first
data point to be associated with the command.

3

Poll Interval

Minimum time in tenths of a second to wait before
polling with this command.

4

Count

Number of data word values to be considered by the
function.

5

Swap Type Code

Swap type code for command: 0=None, 1=Swap words,
2=Swap words & bytes and 3=swap bytes in each word.

6

Node Address

Address of unit to reach on the data highway.

7

Function Code = 5

Unprotected Write Function

8

Word Address

Word address where to start the write operation.

P1

9 to 11

Not Used

These fields are not used by the command. Values
entered in these columns will be ignored.

P2 to P4

This function writes one or more words of data to the PLC memory. This function
should work on the following devices: 1774-PLC, PLC-2, PLC-3, PLC-5, SLC
500, SLC 5/03, SLC 5/04 and MicroLogix 1000.

Function Code #100 - Word Range Write (PLC-5 Command) (Binary Address)

Column

Parameter

Description

Parameter

1

Enable/Type Word

0=Disabled, 1=Continuous and 2=Conditional.

2

Virtual Database Address

This parameter defines the database address of the first

data point to be associated with the command.

3

Poll Interval

Minimum time in tenths of a second to wait before
polling with this command.

4

Count

Number of data word values to be considered by the
function.

5

Swap Type Code

Swap type code for command: 0=None, 1=Swap words,
2=Swap words & bytes and 3=swap bytes in each word.

6

Node Address

Address of unit to reach on the data highway.

7

Function Code = 100

Word Range Write Command.

8

File Number

PLC-5 file number to be associated with the command.
If a value of -1 is entered for the parameter, the field will
not be used in the command, and the default file will be

used.

P1

9

Element Number

The parameter defines the element in the file where
write operation will start. If a value of -1 is entered for
the parameter, the field will not be used in the

command, and the default element will be used.

P2

10

Sub-Element Number

This parameter defines the sub-element to be used with
the command. Refer to the AB documentation for a list
of valid sub- element codes. If the value is set to -1, the

default sub-element number will be used.

P3

11

Not Used

This field is not used by the command. Values entered
in this column will be ignored.

P4

This function writes one or more words of data to a PLC data table. This function
should work on the following devices: PLC-5.