Database in SLC

Database in MVI46-DFCM

File

M0 Offset

File

Register

Content

Description

N10:21

22

N32:25

5025

Minimum
Command
Delay

This parameter specifies the
number of milliseconds to wait
between the initial issuance of a
command. This parameter can be
used to delay all commands sent
to slaves to avoid "flooding"
commands on the network. This
parameter does not affect retries
of a command as they will be
issued when failure is recognized.
Valid value in the range of 0 to
65535.

N10:22

23

N32:26

5026

Command
Error Pointer

This parameter sets the address
in the internal DF1 database
where the command error data
will be placed. If the value is set
to -1, the data will not be
transferred to the database. Valid
value of 0 to 4999.

N10:23

24

N32:27

5027

Response
Timeout

This parameter represents the
message response timeout
period in 1-ms increments. This is
the time that a port configured as
a master will wait before re-
transmitting a command if no
response is received from the
addressed slave. The value is set
depending upon the
communication network used and
the expected response time of
the slowest device on the
network.

N10:24

25

N32:28

5028

Retry Count This parameter specifies the

number of times a command will
be retried if it fails. Valid value in
the range of 0 to 10.

N10:25

26

N32:29

5029

Error Delay
Count

This parameter specifies the
number of polls to be skipped on
the slave before trying to re-
establish communications. After
the slave fails to respond, the
master will skip commands to be
sent to the slave the number of
times entered in this parameter.
Valid value in the range of 0 to
65535.

N10:26

27

N32:30

5030

Slave List
Pointer

This parameter specifies the
starting address in the virtual
database where the 256 slave
status values will be written. If the
parameter is set to -1, the slave
data will not be placed in the
database. Valid value in the
range of -1 to 4743.

N10:27

28

N32:31

5031

Slave List
Frequency

Not used in this version of the
software

Advertising