Basic Command Set Functions

Function
Code

Command Function Definition

PLC5

SLC500 &
MicroLogix

Power-
monitor II

ControlLogix

1 0x00

N/A

Protected

Write

X

X

2 0x01

N/A

Unprotected

Read

X X

X

3 0x02

N/A

Protected

Bit

Write

X

X

4

0x05

N/A

Unprotected Bit Write X

X

5 0x08

N/A

Unprotected

Write

X X

X

PLC-5 Command Set Functions

Function
Code

Command Function Definition

PLC5

SLC500

&

MicroLogix

Power-
monitor II

ControlLogix

100

0x0F

0x00

Word Range Write
(Binary Address)

X

X

101

0x0F

0x01

Word Range Read
(Binary Address)

X

X

102 0x0F 0x26

Read-Modify-Write
(Binary Address)

X

X

150

0x0F

0x00

Word Range Write
(ASCII Address)

X

X

151

0x0F

0x01

Word Range Read
(ASCII Address)

X

X

152 0x0F 0x26

Read-Modify-Write
(ASCII Address)

X

X

SLC-500 Command Set Functions

Function
Code

Command Function Definition

PLC5

SLC500 &
MicroLogix

Power-
monitor II

ControlLogix

501 0x0F 0xA1

Protected

Typed

Logical Read With
Two Address Fields

X

X

502 0x0F 0XA2

Protected

Typed

Logical Read With
Three Address Fields

X X X

509 0x0F 0XA9

Protected

Typed

Logical Write With
Two Address Fields

X

X

510 0x0F 0XAA

Protected

Typed

Logical Write With
Three Address Fields

X X X

511 0x0F 0XAB

Protected

Typed

Logical Write With
Mask (Three Address
Fields)

X

X

Each command list record has the same general format. The first part of the
record contains the information relating to the communication module and the
second part contains information required to interface to the DF1 slave device.