Installing and Configuring the Module

MVI46-DFCM ♦ SLC Platform

DF1 Communication Module

ProSoft Technology, Inc.

Page 27 of 103

October 20, 2008

Database in SLC

Database in MVI46-DFCM

File

M0 Offset

File

Register Content

Description

N10:35

36

N32:44

5044

Termination
Type

This parameter specifies the error
checking for all DF1 messages.
0=BCC, 1=CRC

N10:36

37

N32:45

5045

Baud Rate

This is the baud rate to be used
on the port. Enter the baud rate
as a value

Baud
Rate

Parameter Value

110

110

150

150

300

300

600

600

1200

12 or 1200

2400

24 or 2400

4800

48 or 4800

9600

96 or 9600

14,400

14, 114 or 14400

19,200

19, 192 or 19200

28,800

28, 288 or 28800

38,400

38, 384 or 38400

57,600

57 or 576

115,200 115 or 1152

N10:37

38

N32:46

5046

Parity

This is the Parity code to be used
for the port. The coded values are
as follows: 0=None, 1=Odd,
2=Even, 3=Mark and 4=Space.

N10:38

39

N32:47

5047

Data Bits

This parameter sets the number
of data bits for each word used by
the protocol. Valid value in the
range of 5 to 8.

N10:39

40

N32:48

5048

Stop Bits

This parameter sets the number
of stop bits to be used with each
data value sent. Valid value of 1
or 2.

N10:40

41

N32:49

5049

Minimum
Response
Delay

This parameter sets the number
of milliseconds to wait before a
response message is sent out of
the port. This parameter is
required when interfacing to a
slow responding device. Valid
value in the range of 0 to 65535.

N10:41

42

N32:50

5050

RTS On
Delay

This parameter sets the number
of milliseconds to delay after RTS
is asserted before the data will be
transmitted. Valid value in the
range of 0 to 65535.

N10:42

43

N32:51

5051

RTS Off
Delay

This parameter sets the number
of milliseconds to delay after the
last byte of data is sent before the
RTS modem signal will be set
low. Valid value in the range of 0
to 65535.