7 command control – ProSoft Technology MVI46-DFCM User Manual

Page 32

Advertising
background image

MVI46-DFCM ♦ SLC Platform

Installing and Configuring the Module

DF1 Communication Module

Page 32 of 103

ProSoft Technology, Inc.

October 20, 2008

Database in SLC

Database in MVI46-DFCM

File

M0 Offset

File

Register

Content

Description

N/A

N/A

N45:27

7627

Command Block
Count

This field contains the total number of
command blocks received from the
processor.

N/A

N/A

N45:28

7628

Error Block
Count

This field contains the total number of
block errors recognized by the module.

N/A

N/A

N45:29

7629

Port 1 Current
Error/Index

For a slave port, this field contains the
value of the current error code returned.
For a master port, this field contains the
index of the currently executing
command.

N/A

N/A

N45:30

7630

Port 1 Last
Error/Index

For a slave port, this field contains the
value of the last error code returned. For
a master port, this field contains the
index of the command with an error.

N/A

N/A

N45:31

7631

Port 2 Current
Error/Index

For a slave port, this field contains the
value of the current error code returned.
For a master port, this field contains the
index of the currently executing
command.

N/A

N/A

N45:32

7632

Port 2 Last
Error/Index

For a slave port, this field contains the
value of the last error code returned. For
a master port, this field contains the
index of the command with an error.

A data file should be allocated in the ladder logic to hold this block of data. The
size of the block of data is 33 words.

2.2.7 Command

Control

Database in SLC

Database in MVI46-DFCM

File

M0 Offset

File

Register

Content

Description

N/A

N/A

N46:0

7800

Command Code Enter one of the valid control command

codes in this register to control the
module (9997, 9998 or 9999). Refer to
the Reference chapter for more
information.

N/A N/A N46:1

to

N46:199

7801 to
7999

Command Data Reserved for future use