77bupload parameter text list, 43baccess time programs, 44bglobal time programs – Honeywell EN2Z-0906GE51 R0708 User Manual

Page 120: Procedures, Record trend data, Historical trend

Advertising
background image

ARENA / RANGER

USER GUIDE

EN2Z-0906GE51 R0708

120

You can define a time window (“Last xx minutes”) and a time range (“Stop after yy

hours”).

ARENA will automatically displaying the controller values. After the elapse of the

time window, the oldest values will begin disappearing and new values will be added

on.

This will be continued until the time range has elapsed. Thus, you are shown the

actual values for the last xx minutes until yy hours have elapsed.

Example: Last = 15 minutes, Stop after: 6 hours

Trend data of the latest 15 minutes is continuously saved and
displayed within 1 day after starting the trend.

The values can be saved to the ARENA database for performing a historical trend

later.

NOTE: Live trend is only possible on site level and on levels below and ARENA

must be connected.

Trend Templates

Each trend is based on a template which saves the trended datapoints (not the

values) and display settings (display type, time interval). Thus templates allow the

easy reuse of trend settings once defined. ARENA provides two default templates,

the Live trend template for Live trends and the Historic trend template for historical

trends. Before firstly using a default template it contains only the display settings but

no datapoints. New templates can be created.

Trend Data Export

Trend data can be exported as .CSV file to MS Excel.

Trending and System Performance

Trending increases bus traffic and requires system resources. Hence, for historical

trends, it is recommended to avoid adding more datapoints to trend than absolutely

necessary. For Live trends, it is recommended to avoid storing datapoints in the

database unless absolutely necessary.

Procedures

For both trend types, the basic procedure can be described as:


1. Record Trend Data

Here you select datapoints to be trended. For historical trends, the values of the
selected datapoints are continuously saved in the ARENA database. For Live
trends, the values of the selected datapoints are not saved in the database by
default, but they can be saved during the live trend when Analyzing the Trend
Data in step 2.

2. Analyze Trend Data

Here you do the following:

• Select datapoints for display

• Configure

display

• Define time interval and

• Start

trending


Record Trend Data

Historical Trend

Here you select the datapoints to be trended. The values of the selected datapoints

are continuously saved in the ARENA database. This collection of trend data occurs

in the background.

NOTE: Historical trend is possible on all levels (station, site, controller, etc.) and in

connected and disconnected states of ARENA.