Cross Reference of iLON 10 Settings and ARENA Settings

ARENA configures the iLON 10 when creating the site (see in “Create Site” section).

If the iLON 10 configuration, e.g. user name or password, was changed manually

afterwards, the ARENA settings must be changed accordingly. If ARENA settings

and the iLON 10 settings are out of sync it may happen that the iLON 10 cannot be

contacted anymore. For the accommodation of settings, use the following table.

General Settings page of iLON 10

iLON 10 Setting

ARENA Setting

Comment

IP Address

Outgoing connection: Remote Site IP

Address

Used in LAN scenarios to contact the iLON

10. User needs Administrator privilege

Subnet Mask

Outgoing connection: Subnet Mask

Used in LAN scenarios to define the subnet

to which the iLON 10 is connected.
User needs Administrator privilege

Gateway Address

Outgoing connection: Gateway

Address

Used in LAN scenarios to resolve

addressing if the iLON 10 and the

supervisor PC are in different subnets.

Contact the I.T. administrator to get the
gateway’s IP address.

Explicit message -> Message with

Code From / To

-

Used to send an alarm from the controller

to the iLON 10. This has to be set "from 76

to 76" and the setting has to be enabled.

Otherwise no alarms will be sent out via
the iLON 10.

PPP Settings page of iLON 10

iLON 10 Setting

ARENA Setting

Comment

Serial Port Baud Rate

-

Should be set to 57600

Local IP Address for incoming calls

-

IP Address for PPP connections via

modem. This is automatically generated

by the ARENA site administration for
Dial-Up scenarios.

Use Static IP Address-> IP Address

-

IP Address for PPP connections via

modem. This is automatically generated

by ARENA site administration for Dial-Up

scenarios.

Profile 1 -> User Name

Incoming Connection->User Name

User Name which the supervisor PC

uses to authenticate an incoming call

from the iLON 10.

Profile 1 -> Password

Incoming Connection->Password

Password which the supervisor PC uses

to authenticate an incoming call from the

iLON 10.

Profile 1-> Phone Number

Incoming Connection -> Local Phone

Number

Phone number under which the

supervisor PC can be reached for Dial-

Up scenarios.

Profile 1 -> Disconnect if idle for

-

This time out applies if no LON

connection can be made to the alarm

receiver (ARENA). This should never

happen. A good default would be 120
sec.

Profile 1 -> Modem Init String

Incoming Connection -> Advanced

settings -> Initialization string

Init string which the iLON 10 uses each

time it triggers a dial-out via modem. Via

the init strings, special modem

configurations can be made. Typical
examples are:
X0: Do not wait for dial tone
M0 instead M1 to switch off the modem
speaker.
A good default string for many modems

is E0Q0V1S0=0&C1M1
If you need special settings, consult your

modem manual and a description of the