38boverview, Show global alarm list – Honeywell EN2Z-0906GE51 R0708 User Manual

Page 75

Advertising
background image

USER GUIDE

ARENA/ RANGER

75

EN2Z-0906GE51

R0708

NOTE: Both views can be configured separately.

Alarm Handling

When the controller is connected to ARENA, alarms are received automatically as

soon as ARENA is installed or the remote site has been configured correctly using

ARENA's site configuration.

NOTES: Dial-up sites will automatically connect to the supervisor PC in case of a

critical alarm. Alarms from LAN sites can only be received if the LAN site is

connected explicitly. Make sure you connect to a LAN site once it has been

successfully created. After exiting and restarting ARENA, previously

connected LAN sites will be automatically reconnected.

The PANTHER / TIGER controller will always send out critical alarms as

soon as they occur. After alarms have been sent, a "blocking time" of 24

hours becomes active for uncritical alarms. During the blocking time, no

uncritical alarms are sent out. However, if there’s a danger of losing alarms

(because the controller’s alarm buffer is 80 % full), the uncritical alarm will

be sent. Also, if a connection is established during the blocking time (e.g.

as a result of a critical alarm), the pending uncritical alarms are sent.

PANTHER / TIGER controllers try to send a critical alarm to ARENA

directly after it occurred. If ARENA does not respond, the controller repeats

the connection attempt each 5 minutes for ½ hour. After that, it repeats the

attempt to reach ARENA each 4 hours, for 3 days. If ARENA does not

respond for 3 days, the controller stops its attempt to reach ARENA. It will

restart the attempt only after ARENA successfully dials into the site.

Acknowledging Alarms

ARENA allows the operator to document that he has seen an alarm. This is called

“acknowledgement”. Acknowledgements can be made by Email (responding to a

forwarded Email), or manually. The person who has made the acknowledgement is

stored with the alarm and displayed in the alarm history. In case of Email

acknowledgements, the sender’s Email address is an indication for the person who

has made the acknowledgement.

To acknowledge an alarm that has been forwarded by Email, just reply to the alarm

Email (i.e. send it back to ARENA). ARENA will receive the Email via POP3, and will

show the replier´s Email address in the acknowledged by field. If an

acknowledgement has successfully been processed by ARENA, it will be deleted

from the mailbox.

To acknowledge alarms manually, click the alarm(s) in the alarm list and click the
Acknowledge

button on the Global Alarm List pane.

Show Global Alarm List

1. In the tree, click the level (site, system, etc.) for which you want to display

alarms.

2. On the right pane, click Alarms tab.
3. The Global Alarm List is displayed. For description of the properties, please

refer to the “Overview” section.


4. In the Global Alarm List, you can do the following:

Advertising