15barena / ranger versions, 46brecord trend data, 13bmiscellaneous – Honeywell EN2Z-0906GE51 R0708 User Manual

Page 140: Miscellaneous

Advertising
background image

ARENA / RANGER

USER GUIDE

EN2Z-0906GE51 R0708

140

MISCELLANEOUS

Alias Name and NV Name Correspondents for SERVAL Controller

NOTE: It is forbidden to use the slash character ”/” in alias names because this

may result in an unexpected behavior of ARENA.

When trending a SERVAL controller, the following table is helpful for identifying the

network variable names of the corresponding alias names.

Alias Name

Network Variable Name (Trend)

Inputs

Room Temperature

SpaceTempOut

Bypass input

EffectOccMode

Digital input2

State

WindowOut.state

Sensor

Digital input 1

Sensor.contact_state_DI1

Setpoint

wheel

input

Sensor.remote_set_point

Outputs

Active Setpoint

EffectSetPnt

Output Status

Heating output signal

UnitStatus.heat_output_primary

Cooling output signal

UnitStatus.cool_output

Fan

speed

UnitStatus.fan_output

Parameters

Wall module

Min Limit Setpoint Pot

WallMod.si_low_setpt

Max Limit Setpoint Pot

WallMod.si_high_setpt

Bypass

Time

WallMod.ui_bypass_time

Control Settings

Cooling Fan Stage 3 Switching Level

CntrlSettings.switch_level_cool

Heating Fan Stage 3 Switching Level

CntrlSettings.switch_level_heat

Temperature SetPoint

Cooling Occupied Setpoint

TempSetPts.occupied_cool

Heating Occupied Setpoint

TempSetPts.occupied_heat

Cooling Standby Setpoint

TempSetPts.standby_cool

Heating Standby Setpoint

TempSetPts.standby_heat

Cooling Unoccupied Setpoint

TempSetPts.unoccupied_cool

Heating Unoccupied Setpoint

TempSetPts.unoccupied_heat

Energy Management

Cooling Recovery Ramp

EnergyManag.optstart_cool_grad

Heating Recovery Ramp

EnergyManag.optstart_heat_grad

Control Parameters

Cooling Proportional Band

FcuGains.si_pid_cool_Xp

Heating Proportional Band

FcuGains.si_pid_heat_Xp

Cooling Integral Time

FcuGains.si_pid_cool_Tn

Heating Integral Time

FcuGains.si_pid_heat_Tn

Advertising