4 AUXILIARY AND APPLIED FUNCTIONS

(4) Network configuration which MELSECNET/10(H), Ethernet, CC-

Link, RS-422/485 were mixed

(a) When the MELSECNET/10(H) or Ethernet is defined as "Network" and CC-

Link or RS-422/485 is defined as "Link", combination of whether to be able
to access from the programming software packages (GX Developer,
MT Developer, etc.) is shown below.

Network communications

Usable/

unusable

Programming software package CPU (C24) Network Link CPU

Programming software package CPU (C24) Link Network CPU

Programming software package Network Link CPU

Programming software package Link Network CPU

Programming software package CPU (C24) Network Link Network CPU

Programming software package CPU (C24) Link Network Link CPU

Programming software package Network Link Network CPU

Programming software package Link Network Link CPU

: Usable : Unusable

(b) It can be accessed to 8 network points by setting the routing parameter in

the "Network".

(c) Because routing cannot access, it can access only the connected network.

The connected network can be selected by specifying the I/O No. of the
module.

RS-232

USB/
RS-232

C24
MNET
Ether

: Serial communication module
: MELSECNET/10(H)
: Ethernet

<Example 1>

Network No.1

Personal computer

Q173D
CPU

C24

MNET

or

Ether

QnUD(H)
CPU

Personal
computer

MNET board or Ether

Personal
computer

Network
No.2

Q173D
CPU

MNET

or

Ether

QnUD(H)
CPU

Q173D
CPU

MNET

or

Ether

QnUD(H)
CPU

MNET

or

Ether

Q173D
CPU

MNET

or

Ether

QnUD(H)
CPU

C24

Q173D
CPU

MNET

or

Ether

QnUD(H)
CPU

Q173D
CPU

MNET

or

Ether

QnUD(H)
CPU

MNET

or

Ether

Network No.3

Q173D
CPU

MNET

or

Ether

QnUD(H)
CPU

CC-Link

Q173D
CPU

CC-Link

QnUD(H)
CPU

Network No.5

C24

CC-Link CC-Link

: Communication is possible
: Communication is possible (Setting of the routing parameter is necessary.)
: Communication is impossible

Q173D
CPU

MNET

or

Ether

QnUD(H)
CPU

Q173D
CPU

MNET

or

Ether

QnUD(H)
CPU

RS-422/485

RS-422/485

Network No.4

RS-422/485

Advertising