3 - 16

3 COMMON PARAMETERS

(2) I/O number assignment of Motion CPU control module

Mitsubishi recommends that I/O No. assignment be set as common consecutive
No. throughout all CPUs.
However, the I/O number of the input modules, output modules and input/output
composite modules controlled with the Motion CPU can also be set regardless as
the I/O number of PLC CPU.
(I/O number of the Motion CPU control modules is indicated as PX/PY.)
I/O number of the Motion CPU control modules cannot be assigned by I/O
assignment settings of PLC CPU.

CPU No. 2

control

module

PX0 to PX1F

(X0 to X1F)

Q173D
CPU

Q03UD
CPU

P

ow

er supp

ly

m

odul

e

X40 to X5F

1

2

3

4

5

0

I/O assignment

Y60 to Y7F

CPU No. 1

CPU No. 2

CPU No. 2

control

module

CPU No. 1

control

module

CPU No. 1

control

module

QX41

PY20 to PX3F

(Y20 to Y3F)

QY41

QX41

QY41

(3) Setting of the Motion CPU control modules by the PLC CPU

Follow the table below when Motion CPU control modules are set in I/O
Assignment Settings of the PLC CPU. (The PLC CPU handles the Q172DLX,
Q172DEX and Q173DPX as intelligent function modules having 32 occupied
points.) Type and number of points may be left unset.

Module name

Type

Number of points

Remarks

Input module

Input

Output module

Output

Input/Output composite
module

Composite I/O

Selected according
to the module.

Analogue input module

Analogue input

Analogue output module

Analogue output

Interrupt module (QI60)

Interrupt

16 points

Q172DLX 32

points

Q172DEX 32

points

Q173DPX

Intelligent

32 points

• For the control CPU,

set the CPU that
corresponds to the
Motion CPU (required).

• Type and number of

points may be left
unset.


POINT

(1) Set the I/O device of the Motion CPU within the range from PX/PY000 to

PX/PYFFF. Set the number of real I/O points within 256 points. (I/O No. may
not be consecutive.)

(2) As for the Motion CPU, the Q172DLX, Q172DEX, Q173DPX and QI60 are not

included in the number of real I/O points.