2 MULTIPLE CPU SYSTEM

(3) Operation at a Motion CPU error

Operations at a Motion CPU error are shown below.

Category

Type of error

Operation

Remark

System setting error

Does not operate from the
beginning (does not run).

• All actual output PY points turn OFF.

No effect on other CPUs.

WDT error

Varies depending on the error.

Self-diagnosis error

Stops at a CPU DOWN error.

• All actual output PY points turn OFF.

Other CPUs may also stop depending on
the parameter setting.

Operation
disable errors

Other CPU DOWN error

Operation corresponding to
STOP (M2000 OFF). Depends on
the "Operation mode upon CPU
stop error" setting.

• All actual output PY points turn OFF.

Self-diagnosis error

Operation continues when the
continuous error occurred.

Motion SFC error
Minor error
Major error
Servo error

Operation
continuous
enable errors

Servo program setting
error

Processing stops for each
program or axis instead of the
Motion CPU stopping all the
processing.

• Only the applicable program stops (the

program may continue depending on the
type of error).

• Actual output PY retains output.
• No effect on other CPUs.