4 AUXILIARY AND APPLIED FUNCTIONS

(b) Operation procedure to connect

1) Turn ON the power supply of the servo amplifier.

2) Set "-10: Connect command" in SD803.

3) Check that "-1: Connect execute waiting" is set in SD508.

(Connect execute waiting)

4) Set "-2: Connect execute command" in SD803.

5) Check that SD508 is "0: Connect command accept waiting" is set in

SD508.
(Completion of connection)

6) Resume operation of servo amplifier after verifying the servo ready

status (M2415+20n) is ON.

(4) Flow for device value at connect/disconnect operation is shown below.

(a) Disconnect operation

SD803

0

SD508

-1

-2

0

1 to 32

-2

0

0

Command

Monitor

Disconnect command
accept waiting

Disconnect command
(Axis No. of servo amplifier
to disconnect)

Disconnect execute
waiting

Disconnect execute
command

Disconnect
processing execute

Completion of
disconnection

Disconnect
command clear

(b) Connect operation

SD803

0

SD508

-1

-2

0

-10

-2

0

0

Command

Monitor

Connect command
accept waiting

Connect command

Connect execute waiting

Connect execute command

Connect processing execute

Completion of
connection

Connect command clear