Appendix 2 system setting errors, Appendices, Table 2.1 system setting errors – MITSUBISHI ELECTRIC MOTION CONTROLLERS Q172DCPU User Manual

Page 148

Advertising
background image


APP - 13

APPENDICES

APPENDIX 2 System Setting Errors

Motion CPUs generate a system configuration error under the following conditions.

Table 2.1 System Setting Errors

Error name

7-segment LED

(Note-1)

Error code

(Note-2)

Error cause

Check

timing

Operation at

error

occurrence

LAY ERROR
(SL

)

• The slot set in system settings is vacant or a different

module is installed.

AXIS No. MULTIDEF

• The axis No. setting overlaps in the system settings.
• The axis No. (function select switch) setting of servo

amplifier overlaps in the same SSCNET system.

AMP No. SETTING

• Not a single axis is set in system settings.

SYS.SET DATA ERR

• System setting data is not written.
• System setting data is written without relative check.

Or it is written at the state of error occurrence.

AXIS No. ERROR

• System setting data is not written.

I/O POINTS OVER

• The number of actual I/O points set in system

settings exceeds 256.

ROM ERROR1

• Type of the operating system software of data written

to ROM is different.

ROM ERROR2

• Data is not written to ROM.

ROM ERROR3
(

)

• Data size of ROM is abnormal.

• Execute the ROM writing again.
• Check the adjustment for the version of Motion

CPU, MT Developer and operating system
software.

ROM ERROR4
(

)

• Data of ROM is abnormal.

• Execute the ROM writing again.
• Check the adjustment for the version of Motion

CPU, MT Developer and operating system
software.

CAN'T USE SL (

)

• The motion modules that cannot be used are

installed.

• Use the Motion modules (Q172DLX, Q173DPX,

Q172DEX).

UNIT SET ERR
(

)

"AL" flashes

3- times

"L01" display

10014

(Note-3)

• The system setting data that set the motion modules

that cannot be used are written.

• Use the MT Developer of version corresponding

to the Motion modules (Q172DLX, Q173DPX,
Q172DEX).

Power
supply ON/
Reset

Cannot be
started.
(Motion CPU
system
setting error)

(Note-1) : "" AL" flashes 3-times "L01" display"" (Repetition) Error code is not displayed.
(Note-2) : Error code stored in self-diagnostic error (SD0)
(Note-3) : When the error code 10014 occurs, the system setting error flag (M2041) turns ON and the error name is displayed on the error

list monitor of MT Developer.

Advertising
This manual is related to the following products: