Ex 5/7/11 rt system – MGE UPS Systems EX 7RT User Manual

Page 16

Advertising
background image

1.1

System Electrical Characteristics

Table 3: Power Module Ratings

Part Number

86055

86075

86115

Apparent Power, kVA

5

7

10@ 200/208/250 VAC Output
11@ 220/230/240 VAC Output

Active Power, kW

4

4.9

8@ 200/208/250 VAC Output
7.3@ 220/230/240 VAC Output

Input Current, A

25/24/23/

35/34/32

50/48/50/48/46/40

22/21/20

31/30/28

Input Voltage, VAC

200/208/220/

200/208/220/

200/208/220/230/240/250

230/240/250

230/240/250

Output Current, A

25/24/23/

35/34/32

50/48/50/48/46/40

22/21/20

31/30/28

Output Voltage, VAC

200/208/220/

200/208/220/

200/208/220/230/240/250

230/240/250

230/240/250

CAUTION

Power Module is factory configured at 208Vac, 60 Hz input and output.
Input and Output of the UPS must always be the same.

Table 4: Battery Module Ratings

Part Number

86079

86119

Battery Type

12VDC/7Ah

12VDC/9Ah

Battery Output Voltage

240VDC

240VDC

1.2

Standard Configurations

The EX 5/7/11 RT systems can be set up in tower and rack configurations.

1.2.1

Tower Configuration

Figure 1-1: Tower Configurations with Power Module, Battery Module, and optional Transformer Module.

EX 5/7/11 RT System

Introduction

1 — 4

86-86000-00 A01

www

.mge

ups.

com

www

.mge

ups.

com

E X B

R T

E X

1 1

R T

OFF

ON

BATTERY MODULE
(EXB 5/7/11 RT)

POWER MODULE
(EX 5/7/11 RT)

www

.mgeu

ps.c

om

www

.mge

ups.

com

OFF

ON

BATTERY MODULE

POWER
MODULE

EX 11

RT

EXB

RT

EX RT

Tran

sform

er

EX RT Transformer

www

.mge

ups.

c

om

Standard Configuration

Configuration with Transformer

Advertising
This manual is related to the following products: