Table 3-3: ON/OFF features.

Display

Factory setting

Options

Comments

Cold start

Disabled

Enabled

Start on battery.

Forced reboot

Enabled

Disabled

Enables automatic restart of
the system even if normal AC
source is restored before the
end of the shutdown sequence.

Automatic restart

Enabled

Disabled

UPS restarts automatically
when normal AC source
is restored.

Sleep mode

Disabled

Enabled

Automatic shutdown on battery
if output load level <10%

Remote Command

Enabled

Disabled

Enables shutdown or restart
orders from software.

Table 3-4: Battery features.

Display

Factory setting

Options

Comments

Battery test

Every week

No test/daily/monthly

Pre-Alarm

20%

0 to 100%

Low battery signal;1% increment

Runtime choice

UPS reads # and type

From 65 to 400 Ah

Requires EX 5/7/11RT CLA if

of battery

using options (see section 1.5.4

modules connected.

“Battery extensions cable kit”)

Battery deep discharge

Enabled

Disabled

If disabled, loss of

protection

MGE UPS SYSTEMS,INC.
warranty.

3.2.2

Accessing personalization through external software

Insert the Solution-Pac CD ROM in your CD drive.

At the first Navigator Screen, select "Installation" and follow the instructions to install Personal

Solution-Pac for Windows.

If nothing appears, launch startup.exe

Then go to "Advanced settings" and "UPS settings".

Please note that the Linux/Unix/MacOS versions of Personal Solution-Pac do not include this feature.

3.2.3

Final startup sequence

Press the <ON> button more than 3 seconds.

After UPS internal test sequence, the green LED

goes on.

CAUTION

During the restart, if the Bypass AC source is out of

tolerance, the UPS will generate an output

calibrated 10 msec output interrupt.

15

EX 5/7/11 RT System

Operation

3 — 4

86-86000-00 A01