Ex 5/7/11 rt system – MGE UPS Systems EX 7RT User Manual

Page 42

Advertising
background image

2.8.5

System Connections as Frequency Converter (without Bypass AC Source)

Figure 2-16: Accessing Terminal Blocks for Input and Output power cables.

EX 5/7/11 RT System

Installation

2 — 18

86-86000-00 A01

CAUTION:

Always connect the

earth ground wire first.

1.

Remove the cover plate under the I/O Box.

Remove the jumper connecting L3 and L1.

CAUTION:

Do not connect anything to the

Bypass AC terminal block.

2.

Refer to section 2.8.1 to install normal AC source
and output wires per I/O Box Terminal diagram. Re-
install the cover plate under the I/O Box.

3.

Secure the I/O Box to power module with three
screws.

See section 2.8.3 for connecting EX RT
Transformer, if necessary.

Card Settin

g

s

RS232 Download

66074

UPS

data

Reset

100 10

1 2

ON

ETHERNET

IP=

MAC=00E0D

8

FF

8

55E

2

1

3

OFF

O

OFF

O

OFF

O

To Step-Down

Transformer