Ex 5/7/11 rt system – MGE UPS Systems EX 7RT User Manual

Page 52

Advertising
background image

3.5

Return of Normal AC source

After an outage, the UPS restarts automatically when AC power is restored (unless this function has been disabled

via UPS personalization).

3.6

Shutdown

Figure 3-7: Shutdown display, circuit breaker, and AC source switch.

EX 5/7/11 RT System

Operation

3 — 8

86-86000-00 A01

1.

Press the OFF button

more than 3

seconds.

The load is no longer protected by the UPS. It is
powered via the bypass AC source. If the UPS is
set in frequency converter mode, the load will not
be powered.

If the bypass AC source is out of tolerance, the
UPS will generate a calibrated 10msec output
interrupt.

2.

Set the battery circuit breaker(s)

to the

OFF position.

3.

Set the Normal AC source circuit breaker

to the OFF position.

4.

For a full shutdown of UPS and connected

load, the upstream circuit breaker (not

included) should be set to the OFF position.

8

14

19

OFF

ON

17

19

8

14