Ex 5/7/11 rt system – MGE UPS Systems EX 7RT User Manual

Page 56

Advertising
background image

4.3

Hot Swapping the Power Module

This operation can be performed without interrupting the load.

Figure 4-1: Disconnecting the power module.

EX 5/7/11 RT System

Maintenance

4 — 4

86-86000-00 A01

1.

Stop the UPS with the OFF button

(press

more than 3 seconds).

Check if UPS is on bypass AC source:

LED

is on (If LED

is not on, do not

turn the manual bypass and call the after sales

support department).

2.

Turn the manual bypass switch

to the

BYPASS position.

3.

Switch the battery circuit breaker(s)

to the

OFF position.

CAUTION:

Do not switch the Normal AC

source circuit-breaker

to

the OFF position. Doing so

will disconnect power to the

load.

4.

Loosen three screws to remove the
Input/Output box.

5.

Disconnect the battery cables

and

from the power module.

The power module can be replaced.

The connected equipment is powered by the

Bypass AC source.