Installation and User Manual

4.4

Re-connecting the power module

This operation can be performed without interrupting the load.

Figure 4-2: Reconnect the power module.

Maintenance

4 — 5

86-86000-00 A01

1.

Secure the Input/Output junction box using the

three screws.

2.

Reconnect the cables

and

to the

power module.

3.

Switch the battery circuit breaker(s)

to the

ON position.

4.

Check if Normal AC source circuit breaker

is on the ON position.

5.

Check that the LED

is on.

6.

Turn the manual bypass switch from the

BYPASS to the NORMAL position.

7.

Follow initial start up sequence (see section

3.1) in order to personalize the UPS.

8.

Push the ON button

for more than 3

seconds.

The green LED

is on, and the connected

equipment is now protected by the UPS.